The inner vertex detector of the IDEA detector concept is based on MAPS technology, and is expected to dissipate less than about 50 mW/cm2. With such low power density air-cooling solutions can be developed. Two main mechanical arrangements for the silicon sensors are envisaged at the moment:a ‘traditional’ flat version, in which MAPS are put on top of a carbon fibre stave, and a curved sensor version, inspired to the ALICE ITS3 vertex detector. Preliminary simulations of the former geometry show that air-cooling can be successfully employed to maintain temperature control along the full length of the stave, which in the case of the longest structures are of the order of 50 cm dimensions,
although with a considerable air-flow, that in turn induces vibrations smaller than the single hit resolution of the MAPS (~3 μm). The mechanical layout of such a solution should guarantee sufficient air-cooling capabilities and keep the mechanical structure vibrations at the minimum.
To validate the effectiveness of this approach, a dedicated experimental setup has been implemented,enabling precise measurements of pressure, temperature, and flow rate within the test section for both single-layer and multi-layer configurations. The experimental system provides essential feed-back to the parallel computational fluid dynamics (CFD) studies, ensuring accurate data interpretation and reliable modelling of the airflow behaviour around the vertex detector staves. The presentation will provide a description of the mechanical and thermal solutions adopted to establish a hermetically sealed volume within the test section, in which cable routing constraints, together with the requirement to ensure efficient assembly and disassembly procedures, have represented significant technical challenges.
Presentation of the results on air-cooling performance as a function of the air-flow obtained by experimental measurement will be presented, and critically discussed.